Clearances to combustible materials
Combustible materials are defined as wood, fabrics, or other materials likely to combust if exposed to flame. Generally, any mate-
rial, which is likely to discolour, melt or misshape when exposed to moderate heat, should be considered as a combustible mate-
r
ial or surface.
Clearance to the sides of the appliance are 100mm (4”) but curtains, drapes and other fabrics are not permitted within a dis-
tance of 500mm (20”) of the appliance sides. No such materials are permitted directly above the appliance regardless of distance.
T
he minimum clearance to the ceiling above the appliance is 800mm (31.5”) measured from the top of the appliance glass panel.
Combustible materials should not be positioned directly in front of the appliance within a distance of one metre.
Under no circumstances should any electrical equipment e.g. plasma/LCD screen TV sets etc. be positioned on the wall above
the appliance. The appliance is designed to be wall mounted alone and not in conjunction with any type of combustible fire sur-
round. No combustible shelves should be positioned on the wall above the appliance. It should be established that any mirrors
or picture frames etc. to be positioned on the wall above the appliance are able to withstand prolonged exposure to moderate
heat and moisture before proceeding with their installation.
The back of the appliance may be installed directly onto a combustible wall, providing it is relatively flat and does not interfere
with the various vent holes in the back panel of the appliance. The wall must be structurally sound and constructed from a mate-
rial capable of withstanding moderate heat. Brick, concrete, finished plaster, most types of conventional wall paper and dry-lined
plasterboard are examples of suitable materials. Materials such as flock, blown vinyl and embossed paper which are sensitive to
even small amounts of heat should be avoided as scorching and or discolouration may occur over time.
If the appliance is to be mounted on a dry lined wall or a timber framed construction wall then the integrity and ability of the
wall to carry the weight of the appliance must be confirmed. It is important in these circumstances that any vapour control bar-
rier is not damaged, and that any structural members of the house frame are not damaged - refer to section 7.0 of the installa-
tion section of these instructions.
The appliance must not be positioned vertically within 100 mm (4”) of a carpeted floor, rugs or fabric materials of any kind. This
dimension is measured vertically to the bottom of the appliance firebox.
Purpose provided ventilation of 100cm
2
MUST be provided for this appliance. An openable window or equivalent is also
required. Any ventilation fitted must comply with local Codes and/or Regulations. Ventilation fitted under, or within immediate
vicinity of the appliance must not be used as it may adversely effect performance of the combustion monitoring system (ODS)
system. The appliance shall not be installed within 1 metre of any existing air vent, and any new air vent shall not be installed
within 1 metre of the appliance. Ventilation openings should never be blocked or restricted in any way.
The requirements of other appliances operating in the space or room must be taken into consideration when assessing ventila-
tion requirements, this will have been carried out by your installer. A supply of fresh air into the room is advisable to maintain
temperatures within limits.
P23 and L23 models : The room size should be a minimum of 23m
3
(e.g. 3.07m x 3.07m x 2.45m or 10'1" x 10'1" x 8').
L30 models : The room size should be a minimum of 30m
3
(e.g. 3.5m x 3.5m x 2.45m or 11'6" x 11'6" x 8').
This is to allow adequate circulation of air and ensure the correct operation of the fire. This volume may include adjacent spaces
but these spaces must not be separated by a door. Note : To calculate a room size in cubic metres (m
3
) divide the room volume
in cubic feet (ft3) by 35.3.
It should be noted that heaters create warm air currents. These currents move heat to wall surfaces next to the heater. Installing
the heater next to vinyl or cloth wall coverings or operating the heater where impurities in the air (such as tobacco smoke, can-
dle smoke etc.) exist, may cause the walls to become discoloured.
This appliance is intended as a secondary source of heat only and should not be used in a room without some form of back-
ground heating present. If the appliance is used in a room as the sole source of heat, then condensation may occur on colder
surfaces within the room.
3.0 VENTILATION & ROOM SIZE
2.0 CLEARANCES TO COMBUSTIBLES - (
CONTINUED)
© 2008 Smeg S.p.A.
GB IE
GB-IE-2
Smeg EU-wide instal instruc-v7-English.qxp:Smeg EU-wide installation instructions DRAFT A-12-12-07.qxd 17/7/08 12:07 Page 13